Omron NB HMI Communication Error: PLC Cable, Port, and Settings

An Omron NB HMI communication error usually comes down to one of four things: the wrong PLC driver, the wrong COM port, a cable that does not match the selected electrical interface, or communication parameters that differ between the HMI and PLC.

Table of Contents

The message on the screen may say PLC No Response, but that does not automatically mean the PLC has failed. An NB panel can download a project normally over USB while its PLC cable is connected to the wrong port. It can also ping an Ethernet PLC while using the wrong protocol or FINS node settings.

This guide focuses on the standard Omron NB Series and NB Series (-V1) panels programmed with NB-Designer, including NB3Q, NB5Q, NB7W, and NB10W models. The NB-S series has its own user manual and connection restrictions. Always confirm the complete HMI model and PLC model before applying a cable diagram or port setting.

What Does the Omron NB Communication Message Mean?

For a serial connection, an NB panel may display a message such as:

PLC No Response: 00-01-01

Omron explains this format as:

PT number – PLC station number – PT serial port number

In the example above, PT No. 0 has lost communication with PLC station 1 through COM1. Port suffix 01 represents COM1 and 02 represents COM2.

For Omron Ethernet UDP drivers, the same style of message identifies the PT, PLC node, and port information used by that connection. Read it with the driver type in mind rather than assuming every number has the same meaning on serial and Ethernet projects.

There is also an important difference between these two messages:

  • PLC No Response: The NB did not receive a reply. Look first at the cable or network path, selected port, station or node, protocol, and PLC communication service.
  • PLC Response Error: The PLC returned an abnormal response to an HMI read or write request. The link may be working, but an address, command, driver, access condition, or FINS conversion setting is wrong.

Record the full message before restarting the panel. A photograph of the error, HMI nameplate, PLC model, and cable ends is usually more useful than the statement “the HMI will not connect.”

Quick Reference: Symptoms and First Checks

SymptomLikely areaFirst check
PLC No Response: 00-01-01COM1 link to PLC station 1COM1 assignment, station number, cable, serial parameters
Error suffix ends in 02COM2 connectionWhether the HMI model has COM2 and the cable uses the COM2 pinout
Project downloads over USB, but PLC data is blankPLC host connection is separate from project transferPLC driver, communication port, and PLC cable
PLC Response ErrorPLC replied with an abnormal resultDriver, device address, data range, read/write permission
Ethernet link is on but no PLC data updatesProtocol or application settingHMI driver, PLC IP, UDP/TCP port, node ID, PLC service
Only one screen produces the errorInvalid object or addressAddresses, data lengths, macros, alarms, and background objects
Communication is slow after opening a screenPolling load or retriesDiscontinuous addresses, logging, macros, timers, and baud rate
Communication drops when a motor or contactor operatesNoise or cable routingShielding, grounding, separation from power wiring
Error starts after replacing the HMIModel or port mismatchFull suffix, COM1/COM2 capability, Ethernet option, downloaded project

Safety Before Handling HMI or PLC Cables

The NB serial ports are not intended for hot plugging. Before disconnecting a D-sub connector, rewiring RS-422A/RS-485 terminals, or moving a communication cable inside a panel:

  1. Stop the machine in a controlled condition.
  2. Follow the site’s lockout and electrical-safety procedure.
  3. Isolate the relevant power sources.
  4. Confirm that hazardous voltage is absent before touching conductors.
  5. Back up the NB-Designer project and PLC program.

Omron also instructs users to keep communication connector screws tightened. Avoid placing cable weight or door movement on the HMI connector.

Need a Replacement Altivar Drive?

Browse new original Altivar drives for maintenance, troubleshooting, and replacement projects.

schneider ATV320 (1)

Step 1: Identify the Exact NB Model and Port

The port arrangement is not the same across the NB family. This is one of the main reasons a cable that worked on an NB7W does not work when moved to an NB3Q.

NB model familyCOM1COM2Ethernet
NB3QRS-232C/RS-422A/RS-485, one mode at a timeNot fittedAvailable on TW01B and TW01B-V1 models
NB5QRS-232CRS-232C/RS-422A/RS-485, one mode at a timeAvailable on TW01B and TW01B-V1 models
NB7WRS-232CRS-232C/RS-422A/RS-485, one mode at a timeAvailable on TW01B and TW01B-V1 models
NB10WRS-232CRS-232C/RS-422A/RS-485, one mode at a timeFitted on the listed TW01B and TW01B-V1 models

The serial interfaces are non-isolated. Omron specifies a maximum transmission distance of 15 m for RS-232C and 500 m for RS-422A/RS-485, subject to the connection method and cable requirements in the manuals.

The point that matters in practice is simpler:

  • NB3Q has only COM1. Its COM1 combines RS-232C, RS-422A, and RS-485 pins.
  • NB5Q, NB7W, and NB10W use COM1 for RS-232C and COM2 for the multi-interface serial connection.

The Host Connection Manual warns that cable diagrams marked for COM2 on NB5Q/NB7W/NB10W must not be copied blindly to the NB3Q COM1 connector. Check the NB3Q pin definitions separately.

Also check the model suffix before troubleshooting Ethernet. A TW00B or TW00B-V1 NB3Q, NB5Q, or NB7W does not have the Ethernet interface found on the corresponding TW01B model.

Step 2: Check the PLC Driver and Network Configuration in NB-Designer

Open the project in NB-Designer and inspect the Configuration and Setup Window. The drawn network should match the equipment physically connected to the HMI.

Check each PT and PLC object for:

  • Exact controller manufacturer and family
  • Communication protocol
  • HMI port or network interface
  • Master/slave role where applicable
  • PLC station or node number
  • Baud rate and serial frame format
  • HMI and PLC IP addresses
  • UDP or TCP port number

The correct manufacturer name is not enough. Omron CP Series Ethernet UDP, Omron CJ/CS/NJ Series Ethernet UDP, Omron NX Series Ethernet UDP, Omron Host Link, Modbus RTU, Modbus ASCII, and Modbus TCP are different drivers.

For example, a CP1L with built-in Ethernet must be configured with the supported CP Series Ethernet driver, not simply left on the project’s default CJ/CS/NJ driver. A protocol mismatch can stop compilation or produce a panel that never receives usable PLC data.

One physical COM port cannot run multiple communication systems at the same time. If two host objects are assigned to COM1, fix the network design instead of increasing the timeout.

After correcting the project, compile it and review every warning before downloading. Keep the edited NB-Designer file as the new master copy; otherwise the next service download may restore the bad settings.

Step 3: Verify the PLC Cable, Not Just the Connector

A D-sub 9-pin plug is a connector shape, not a communication standard. The cable must match:

  • The exact NB model
  • COM1 or COM2
  • RS-232C, RS-422A, or RS-485
  • The PLC CPU or communication module
  • The selected protocol
  • Any required adapter or termination

Omron lists the following standard NB-to-PLC accessories:

  • XW2Z-200T: 2 m RS-232C cable for supported CP/CJ/CS PLC connections
  • XW2Z-500T: 5 m RS-232C cable for supported CP/CJ/CS PLC connections
  • NB-RSEXT-2M: 2 m cable for supported RS-422A/RS-485 connections

These part numbers are not universal for every PLC or third-party controller. Use the Host Connection Manual chapter for the selected driver to confirm the complete system configuration and wiring diagram.

Why COM1 and COM2 cables are not interchangeable

Omron explicitly warns that COM1 and COM2 communication cables are not interchangeable. The pin functions differ, even though both connectors may be D-sub 9-pin.

For a user-built cable, check every conductor end to end. Look for:

  • Transmit and receive pins crossed correctly for RS-232C
  • Signal ground connected as specified
  • Correct RS-422A transmit and receive pairs
  • Correct RS-485 polarity
  • Connector gender and pin numbering viewed from the correct side
  • Loose crimp contacts or false solder joints
  • Shield and termination installed as shown in the manual
  • Connector screws fully secured

Do not match terminals only by labels such as A and B. Manufacturers do not always use those labels with the same polarity convention.

If a machine is down and the original cable identity is uncertain, Kwoco can help match an Omron NB cable, HMI, PLC option board, or replacement unit. Send the complete HMI and PLC model numbers, clear photos of both connectors, the port being used, and the NB-Designer protocol setting. That is enough to avoid most connector-only guesses.

Find the Right PLC for Your System

Explore new original PLC CPUs, I/O modules, power supplies, and communication units for maintenance and automation projects.

schneider PLC

For an Omron CP, CJ, or CS PLC connected by Host Link, both devices must use the same serial format and speed, and the PLC port must actually be set for Host Link.

The NB Series Setup Manual gives the following Host Link communication settings:

ParameterHost Link setting
Data bits7
Stop bits2
ParityEven
Baud rateAny supported value, but HMI and PLC must match
Unit/station number00 in the documented basic setup

Do not apply this 7-E-2 format to Modbus or a third-party serial driver. It is the Omron Host Link setting described in the NB setup procedure.

In the PLC project, verify:

  • The physical PLC port being used
  • Host Link mode rather than Toolbus, no-protocol, or another serial mode
  • Baud rate
  • Data bits, parity, and stop bits
  • Unit number
  • Option-board or serial-module settings
  • DIP switch settings that determine whether PLC Setup values are active

On CP1L and CP1H models, port 1 and port 2 use different PLC Setup words and may be controlled by front DIP switches. Read the current PLC configuration instead of copying values from another machine.

For CP1E and CP2E models, check the exact CPU and serial option. Omron states that an NB cannot connect to the CP2E built-in two-wire RS-485 port using the Host Link arrangement documented in the setup manual. Use a supported connection method and hardware combination.

Omron’s NB connection guidance uses four-wire RS-422A when extending Host Link distance. Do not assume a two-wire RS-485 port can replace it because both use differential signaling.

Verify the send and receive pairs at both ends, along with termination and signal ground. If communication works at low speed on the bench but fails after installation, inspect cable route, shielding, and topology before raising the baud rate.

Step 5: Fix Ethernet Communication

Ethernet troubleshooting should be divided into network reachability and PLC protocol communication.

Check the live IP settings

Confirm the actual values in the NB project, the NB System Setting Mode, and the PLC project:

  • HMI IP address
  • PLC IP address
  • Subnet mask
  • Default gateway, if routing is used
  • UDP or TCP port
  • Omron FINS network and node number where applicable

For a simple local connection, the HMI and PLC normally need addresses in the same IP subnet and each device must have a unique IP address. When routers are used, verify the gateway and route rather than changing the subnet mask until communication appears.

Models with Ethernet use 10/100BASE-T. Check the RJ45 link indicators, switch power, cable latches, and switch port. Test with a known-good standard Ethernet cable and, where permitted, a simple isolated HMI-to-PLC network.

Match the protocol and port

A successful ping shows that IP packets can reach the PLC. It does not prove that the PLC is listening for the protocol selected in NB-Designer.

For Omron Ethernet UDP connections, the V107 Setup Manual shows the HMI and PLC registered in PT Property > PT > Communication Setting, with matching IP, port, and protocol entries. Its FINS/UDP examples use port 9600, but other protocols have different ports. Do not apply 9600 to Modbus TCP or a third-party PLC without its connection manual.

Check that:

  • The NB driver matches the PLC family.
  • The PLC-side Ethernet or FINS/UDP settings are enabled.
  • The HMI targets the PLC’s actual IP address.
  • HMI and PLC port numbers agree.
  • FINS network and node numbers are valid and unique.
  • A managed switch, VLAN, firewall, or router is not blocking the traffic.

Check FINS node and IP conversion settings

An Omron Ethernet link can be physically healthy but still fail because its FINS addressing is inconsistent.

The network number identifies the FINS network; it is not the same thing as the IP subnet. The node ID identifies the device in that FINS network and must not conflict with another node.

For projects using an IP address table or combined IP/FINS conversion, verify that the NB’s own node ID has not been entered as a remote PLC entry. Omron documents this as one condition that can produce PLC Response Error.

If the error is PLC No Response, trace the PT number, PLC node, and port information shown in the message. If it is PLC Response Error, inspect the returned request: the PLC may be reachable but rejecting an address or command.

Upgrade or Replace Your HMI

Find compatible HMI panels for discontinued models, machine upgrades, and operator interface replacement.

schneider hmi

Step 6: Use NB-Designer Direct Online Test

Omron recommends Direct Online Test to separate parameter problems from the physical NB-to-PLC cable.

The practical sequence is:

  1. Back up the HMI and PLC projects.
  2. Connect the engineering PC to the PLC using the correct PLC programming cable or network path.
  3. Confirm that PLC programming software can go online.
  4. Exit the PLC program-transfer mode.
  5. In NB-Designer, select Tools > Direct Online Test.
  6. Observe whether the test project can read the configured PLC data.

If Direct Online Test fails, compare the NB project driver and communication parameters with the PLC configuration.

If Direct Online Test works but the physical NB does not, focus on the HMI port selection, NB-to-PLC cable, connector pinout, and HMI serial or Ethernet hardware.

This test is far more useful than changing several parameters at once because it removes one part of the path without changing the PLC program.

Step 7: Check Whether Every Screen Fails

All objects have stopped updating

When all PLC values are stale, investigate the shared connection:

  • PLC power and CPU mode
  • Driver and host selection
  • COM1/COM2 or Ethernet interface
  • Cable and switch
  • Baud rate or IP settings
  • PLC communication service
  • Station or node number

Only one screen causes the message

The physical link is probably working. Inspect the objects on that screen for:

  • Unsupported or out-of-range PLC addresses
  • A 32-bit value crossing an invalid word boundary
  • Incorrect array length
  • Read-only or write-protected devices
  • Indirect addresses
  • Macros that access PLC memory
  • Alarm, event, recipe, or trend objects

An invalid read/write request can produce PLC Response Error even while other screens work normally.

The message appears everywhere, but most values work

Look for a background object. Data logs, alarms, event monitoring, PLC Control objects, timers, macros, common sheets, and data history can keep polling a bad address on every screen.

Use a copy of the project to disable suspect groups methodically. Do not tear apart the only working copy.

Step 8: Fix Slow or Intermittent Communication

Slow page changes are often caused by polling load rather than a defective HMI.

Omron lists these common contributors:

  • Too many PLC-linked objects on one screen
  • Large numbers of discontinuous addresses
  • Macros that repeatedly access PLC addresses
  • Too many timers on common sheets
  • Continuous Data Log, XY Graph, or Data History tasks
  • Large alarm and event tables with scattered addresses
  • Too many PLC Control objects
  • Too many connected controllers and communication addresses
  • On-site electrical interference

Group PLC addresses where the control design permits it and lengthen sampling intervals for background functions that do not need fast updates. A larger timeout is not a substitute for reducing unnecessary requests.

If communication drops when an inverter, servo, contactor, or solenoid operates, inspect the installation:

  • Keep communication cable away from power and motor wiring.
  • Use the shielded cable and grounding method specified by Omron and the PLC manufacturer.
  • Check protective-earth and cabinet bonding.
  • Inspect cable damage near hinges and moving machine sections.
  • Check RS-422A/RS-485 termination and topology.

Omron’s troubleshooting guide recommends keeping the communication cable at least 10 cm from power lines. Greater separation may be required by the equipment manuals or site EMC standard.

Step 9: Build a Minimal Test Project

A small test project quickly shows whether the fault belongs to the connection or the application.

  1. Select the exact NB model and suffix.
  2. Add one PLC with the correct driver.
  3. Assign it to the actual COM port or Ethernet interface.
  4. Enter the verified PLC parameters.
  5. Add one read-only display for a known valid, stable PLC word.
  6. Compile and run Direct Online Test.
  7. Download the test project to the HMI only after backing up the production project.

If the minimal project fails in Direct Online Test, revisit the driver and PLC-side settings.

If it passes online but fails on the HMI, revisit the cable, HMI port, and hardware.

If it works on the HMI, the original project’s addresses, macros, background functions, or communication load need to be isolated.

Communication Problems After Replacing an NB HMI or PLC

Do not select a replacement by screen size alone. Before transferring the project, record:

  • Complete NB model, including TW00B, TW01B, and -V1 suffixes
  • Display size and resolution
  • Supply and mounting details
  • COM1 and COM2 use
  • RS-232C, RS-422A, or RS-485 interface
  • Ethernet requirement
  • NB-Designer project and software version
  • PLC model, option board, and firmware
  • Cable part number or verified pinout
  • PLC serial or Ethernet settings

After replacing a PLC, restore its communication parameters as well as the ladder program. A PLC with correct machine logic but a default serial port will still produce PLC No Response.

After replacing an HMI, download the correct model project and verify the port assignment before connecting the PLC cable. A project converted to another NB model can retain communication assumptions that no longer match the rear connectors.

Kwoco can help check a replacement Omron NB HMI, PLC, cable, or communication option against these details. For discontinued or mixed-generation equipment, include the original project version and photographs of the rear ports so electrical compatibility is checked before installation.

Frequently Asked Questions

It means PT No. 0 has lost serial communication with PLC station 1 through COM1. Verify the COM1 assignment, PLC station number, cable pinout, serial format, and PLC port mode. A suffix ending in 02 points to COM2.

It depends on the HMI model and interface. NB3Q has only COM1, which supports one selected RS-232C/RS-422A/RS-485 mode. On NB5Q, NB7W, and NB10W, COM1 is RS-232C and COM2 is the multi-interface RS-232C/RS-422A/RS-485 port.

Not safely as a general rule. The cable must follow the Omron Host Connection Manual for the exact HMI port and PLC. For supported CP/CJ/CS RS-232C connections, Omron lists XW2Z-200T and XW2Z-500T; other PLCs and ports may require different wiring.

Project transfer and PLC communication are separate paths. USB or Ethernet may download the application correctly while the project uses the wrong PLC driver, COM port, station, IP address, protocol port, or physical PLC cable.

Ping confirms IP reachability, not the PLC protocol. Check the NB-Designer driver, PLC IP and port, FINS network and node settings, PLC-side Ethernet service, and requested device addresses. A reachable PLC can still reject an unsupported read or write request.

Power your projects with brand-new, original Omron, Mitsubishi, Schneider PLC – in stock, ready now!

When an HMI Port Is Actually Faulty

Suspect the NB hardware only after configuration and external components have been isolated.

A serial port becomes a credible suspect when:

  • The exact driver and communication parameters are verified.
  • The PLC port communicates with another device.
  • A known-good cable with the correct pinout is used.
  • Direct Online Test succeeds with the same project settings.
  • The NB still sends no valid data or receives nothing on the selected port.

An Ethernet port becomes suspect when it cannot establish a link with multiple known-good cables and switch ports, while the correct Ethernet-capable NB model is being used.

Before replacement, inspect the D-sub connector for bent pins, loose mounting, cable strain, and evidence of hot-plug damage. Keep the production project backup with the machine.

Official Omron References

Contact Us

Just fill out your name, email address, and a brief description of your inquiry in this form. We will contact you within 24 hours.

Hot Sale Products

Omron CPU Unit CJ2M-CPU32

Omron PLC CJ1W-PA202 Supplier in China

Mitsubishi MR-JE Series 400w Servo Drive MR-JE-40A

Need a Fast Match?

Share your model or spec and our team will help you find the right fit-fast.

You May Also Find These Topics Interesting

Ask For A Quick Quote

*we respect your confidentiality and all information are protected.