Mitsubishi MR-J4 AL.16 vs AL.20: Encoder Communication Faults Explained

An MR-J4 encoder alarm does not automatically mean the motor needs replacing. The amplifier has detected a problem communicating with the encoder; the alarm alone does not identify which component caused it.

Table of Contents

The distinction between AL.16 and AL.20 is the communication stage. AL.16 concerns initial communication. AL.20 concerns normal communication after initialization. “Normal communication” does not mean the motor must be turning—an AL.20 fault can occur while the axis is stationary. See Mitsubishi’s MR-J4 Troubleshooting Manual.

This guide focuses on conventional rotary-servo applications using MR-J4-A and MR-J4-B amplifiers. Linear encoders, multi-axis amplifiers and special operating modes have additional checks.

Read the Detailed Code Before Touching the Cable

A maintenance report that says “encoder alarm” leaves too much unanswered. Record the detailed code, affected axis, amplifier model and motor model before disconnecting anything.

The following examples are a partial list, not a complete alarm table.

Detailed codeMeaning, paraphrasedWhy it matters
16.1Receive-data fault during initializationDirects you to the initial communication checks
16.3Another initial receive-data faultIts checks also include configuration and control-power stability
20.1Receive-data fault during normal communicationIncludes cable and shield-termination checks

The detailed-code remedies overlap. They can involve connections, configuration, environmental interference, the encoder or the amplifier. None of these three codes proves that a particular component has failed. Use the applicable model column in the official troubleshooting tables.

Before starting work, capture:

  • The full alarm code and available alarm history.
  • Whether the fault appeared at startup, at standstill or during a particular movement.
  • Any recent motor, cable, amplifier or parameter changes.
  • Whether other axes were affected at the same time.

Keep a parameter backup before making changes. A factory reset can remove useful evidence and introduce a second problem.

Need a Replacement Altivar Drive?

Browse new original Altivar drives for maintenance, troubleshooting, and replacement projects.

schneider ATV320 (1)

Use the Fault Timing to Choose the First Check

The circumstances surrounding the alarm often make the investigation more manageable. Treat them as clues, not proof.

Observed patternUseful next investigation
First appeared after maintenanceCompare the installed parts, connections and settings with the documented configuration
Returns near the same axis positionInspect the corresponding moving-cable section under safe isolation
Appears around contactor or other equipment switchingCompare event timing and review cable routing and shielding
Several axes fail togetherLook for a shared event before assuming several motors failed independently

For example, an alarm that began immediately after a cable replacement deserves a close look at that replacement. Confirm its complete part number and intended application. A connector that fits mechanically is not enough to establish compatibility.

Conversely, a fault that returns at the same point in travel calls for a different investigation. Identify which cable section bends there, then inspect it with the machine safely isolated. Do not try to reproduce the alarm by pulling or bending a live cable.

Inspect the Connections With Power Safely Isolated

Electrical inspection belongs to qualified personnel following the machine’s isolation procedure. Secure any load that could move, isolate the relevant supplies, observe the specified discharge period and verify the equipment is safe before touching connections. Switching off the operator panel is not electrical isolation. Mitsubishi’s MR-J4 safety instructions explain the residual-voltage hazard.

Photograph both ends of the encoder connection before disturbing them. Then examine the connector seating, locking mechanism, contacts, cable entry and strain relief. Look for contamination, damaged contacts, crushing or a cable pulled tight against its connector.

Avoid changing several things at once. If a connector is reseated, a cable replaced and parameters altered in the same intervention, a successful restart will not tell you which change mattered.

A clean-looking cable is not a conclusive test result. If the visual inspection finds nothing, the next step is a suitable electrical or substitution test performed against the correct documentation—not an automatic motor order.

Find the Right PLC for Your System

Explore new original PLC CPUs, I/O modules, power supplies, and communication units for maintenance and automation projects.

schneider PLC

Check Shielding Before Blaming the Encoder

Encoder communication depends on the cable installation as well as the connected equipment.

Mitsubishi’s EMC Installation Guidelines describe shielded encoder cabling and shield grounding at both ends. The MR-J4 safety instructions also call for separation between power and signal cables.

During an inspection, compare the actual installation with those requirements:

  • Has the encoder cable been rerouted alongside power wiring?
  • Was a shield termination disturbed during connector replacement?
  • Has an extension or intermediate connection been added?
  • Did the fault start after another drive or switching device was installed?

An alarm occurring when a contactor switches is worth investigating, but timing alone does not establish electrical noise as the cause. Record the pattern and check the installation before adding filters, ferrites or ground connections.

After a Replacement, Verify the Configuration

If the fault started after an amplifier or motor change, compare the full model numbers with the approved machine configuration. Include suffixes and the cable assembly reference.

Check the relevant communication settings in the manual for that amplifier family. Do not copy a parameter number or value from a different MR-J4 variant. Preserve the original settings and document each change.

Where hardware isolation is necessary, a qualified technician may use a confirmed-compatible, known-good component under a controlled test procedure. Compatibility must be established first. Borrowing a cable or motor from a neighboring axis simply because it looks similar can complicate the diagnosis.

A useful test record states what changed, what stayed unchanged and whether the original fault returned under the same conditions.

Resetting AL.16 and AL.20

For the AL.16 and AL.20 entries, Mitsubishi’s reset table permits power cycling, while ordinary alarm reset and CPU reset are marked unavailable. Correct the cause before restarting; repeated power cycling is not a repair. 

Keep the run command disabled and follow the machine’s restart procedure. Once the axis is ready for a controlled test, verify more than an alarm-free display.

Check startup, the operating condition associated with the original fault and the relevant machine cycle. If work affected position references or mechanical connections, complete the required reference and positioning checks before releasing the machine.

Record the corrective action and test conditions. “Restarted successfully” is a weaker maintenance record than “repaired the damaged connection, then verified startup and the previously failing movement.”

Upgrade or Replace Your HMI

Find compatible HMI panels for discontinued models, machine upgrades, and operator interface replacement.

schneider hmi

Power your projects with brand-new, original Omron, Mitsubishi, Schneider Servo – in stock, ready now!

Before Ordering Replacement Parts

If testing identifies a component that needs replacement, prepare its complete model number, the amplifier and motor nameplate details, cable reference, detailed alarm code and relevant photographs.

Those details make a parts inquiry useful. You can contact Kwoco with that information when checking a replacement requirement.

For alarms outside encoder communication, refer to the broader Mitsubishi MR-J4 Servo Alarm Codes guide.

Contact Us

Just fill out your name, email address, and a brief description of your inquiry in this form. We will contact you within 24 hours.

Hot Sale Products

Omron CPU Unit CJ2M-CPU32

Omron PLC CJ1W-PA202 Supplier in China

Mitsubishi MR-JE Series 400w Servo Drive MR-JE-40A

Need a Fast Match?

Share your model or spec and our team will help you find the right fit-fast.

You May Also Find These Topics Interesting

Request a Quote

*We respect your privacy and keep your information confidential.