Omron CJ1W-AD081-V1 Analog Input Unit
Analog input unit, 8 x inputs 1 to 5 V, 0 to 5 V, 0 to 10 V, -10 to 10 V, 4 to 20 mA, resolution 1:4000 / 8000, screw terminal
Brand | Omron |
Model Number | CJ1W-AD081-V1 |
State | In stock |
Condition | New Original |
Warranty | 12 months |
Categories
- Omron,
- Omron CJ1W
Global Assurance
Item | CJ1W-AD041-V1 | CJ1W-AD081-V1 | CJ1W-AD042 | |||
Unit type | CJ-series Special I/O Unit | |||||
Isolation *1 | Between I/O and Controller signals: Photocoupler (No isolation between I/O signals.) | Between I/O and Controller signals: Digital isolator (No isolation between I/O signals.) | ||||
External terminals | 18-point detachable terminal block (M3 screws) | |||||
Power consumption | 420 mA max. at 5 VDC | 520 mA max. at 5 VDC | ||||
Dimensions (mm) | 31 × 90 × 65 mm (W × H × D) | |||||
Weight | 140 g max. | 150 g max. | ||||
General specifications | Conforms to general specifications for CJ Series. | |||||
Input specifi- cations | Number of analog inputs | 4 | 8 | 4 | ||
Input signal range *2 | 1 to 5 V 0 to 5 V 0 to 10 V – 10 to 10 V 4 to 20 mA *3 | 1 to 5 V 0 to 10 V – 5 to 5 V – 10 to 10 V 4 to 20 mA *4 | ||||
Maximum rated input (for 1 point) *5 | Voltage Input: ± 15 V Current Input: ± 30 mA | |||||
Input impedance | Voltage Input: 1 MΩ min. Current Input: 250 Ω (rated value) | |||||
Resolution | 4,000/8,000 *6 | 1 to 5 V | 10,000 | |||
0 to 10 V | 20,000 | |||||
– 5 to 5 V | 20,000 | |||||
– 10 to 10 V | 40,000 | |||||
4 to 20 mA | 10,000 | |||||
Converted output data | 16-bit binary data | |||||
Accuracy *7 | 25 °C *8 | Voltage Input: ± 0.2% of F.S. Current Input: ± 0.4% of F.S. | ||||
0 °C to 55 °C | Voltage Input: ± 0.4% of F.S. Current Input: ± 0.6% of F.S. | |||||
A/D conversion period *9 | 1 ms/250 μs per point *6 | 20 μs/1 point, 25 μs/2 points, 30 μs/3 points, 35 μs/4 points | ||||
Input functions | Mean value processing | Stores tde last “n” data conversions in tde buffer, and stores tde mean value of tde conversion values. Buffer number: n = 2, 4, 8, 16, 32, 64 | Stores tde last “n” data conversions in tde buffer, and stores tde mean value of tde conversion values. Buffer number: n = 2, 4, 8, 16, 32, 64, 128, 256, 512 | |||
Peak value holding | Stores tde maximum conversion value while tde Peak Value Hold Bit is ON. | |||||
Scaling | — | Setting values in any specified unit witdin a range of ±32,000 as tde upper and lower limits allows A/D conversion to be executed and analog signals to be output witd tdese values as full scale. | ||||
Input disconnection detection | Detects tde disconnection and turns ON tde Disconnection Detection Flag. *10 | |||||
Offset/gain adjustment | Supported | — | ||||
Direct conversion | — | A/D conversion is performed and tde converted value is refreshed when tde ANALOG INPUT DIRECT CONVERSION instruction (AIDC) is executed. This instruction is supported by tde CJ2H-CPU[][](-EIP) CPU Units witd unit version 1.1 or later, and CJ2M-CPU[][]. CJ1, NJ501, and CP1H CPU Units and NSJ Controllers do not support direct conversion. |
Related Product
Get Started Today!
UNLOCK EFFICIENT SOLUTIONS – SUBMIT YOUR REQUEST FOR IMMEDIATE ASSISTANCE.
Embark on a journey of seamless procurement with us. If you’re seeking a product quote or require any additional support, our team is here to guide you every step of the way.
Fill out this form to start a conversation tailored to your specific needs. We understand the value of your project and time.
Rest assured, your email information remains strictly confidential with us. Let’s collaborate to enhance your operations today.