[gtranslate]

Omron DC Input Unit NX-ID6142-6

Digital input module, 32 digital inputs, NPN/PNP 24VDC, designed for the NX series PLCs, suitable for high-speed input tasks.

  • High Input Capacity: 32 points for extensive data collection.
  • Fast Response: ON/OFF response time of 20 μs for quick signal processing.
  • Compact Design: Measures 30 x 100 x 71 mm, optimizing panel space.
  • Power Efficiency: Low power consumption at 1.15 W.
  • Wide Operating Range: Suitable for temperatures from 0 to 55°C.
  • Reliable Communication: EtherCAT support ensures high-speed and robust data transmission.
  • Compliance: Meets CE, UL, and RoHS standards for safety and environmental requirements​​​​.

Categories

Global Assurance

100% new original
12 months warranty
wordwide shipping
Unit nameDC Input UnitModelNX-ID6142-6
Number of points32 pointsExternal connection terminalsFujitsu/OTAX connector (40 terminals)
I/O refreshing methodSwitching Synchronous I/O refreshing and Free-Run refreshing
IndicatorsTS indicator, input indicator 3185_sp_15_1Internal I/O commonFor both NPN/PNP
Rated input voltage24 VDC (19 to 28.8 VDC)
Input current4.1 mA typical (24 VDC)
ON voltage/ON current19 VDC min./3 mA min. (between COM and each signal)
OFF voltage/OFF current5 VDC max./1 mA max. (between COM and each signal)
ON/OFF response time20 μs max./400 μs max.
Input filter timeNo filter, 0.25 ms, 0.5 ms, 1 ms (default), 2 ms, 4 ms, 8 ms, 16 ms, 32 ms, 64 ms, 128 ms, 256 ms
Dimensions30 (W) x 100 (H) x 71 (D)Isolation methodPhotocoupler isolation
Insulation resistance20 MΩ min. between isolated circuits (at 100 VDC)Dielectric strength510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max.
I/O power supply methodSupply from external sourceCurrent capacity of I/O power supply terminalWithout I/O power supply terminals
NX Unit power consumption• Connected to a CPU Unit or Communication Control Unit 0.95 W max. • Connected to a Communi- cations Coupler Unit 0.55 W max.Current consumption from I/O power supplyNo consumption
Weight90 g max.
Circuit layout3185_sp_15_2
Installation orientation and restrictionsInstallation orientation: • Connected to a CPU Unit or Communication Control Unit: Possible in upright installation. • Connected to a Communications Coupler Unit: Possible in 6 orientations. Restrictions: As shown in the following. 3185_sp_15_3
Terminal connection diagram
3185_sp_15_4
• The polarity of the input power supply can be connected in either direction. • Be sure to wire both pins A9 and A18 (COM0), and set the same polarity for both pins. • Be sure to wire both pins B9 and B18 (COM1), and set the same polarity for both pins.
Disconnection/ Short-circuit detectionNot supported.Protective functionNot supported.

Get Started Today!

UNLOCK EFFICIENT SOLUTIONS – SUBMIT YOUR REQUEST FOR IMMEDIATE ASSISTANCE.

Embark on a journey of seamless procurement with us. If you’re seeking a product quote or require any additional support, our team is here to guide you every step of the way.

Fill out this form to start a conversation tailored to your specific needs. We understand the value of your project and time.

Rest assured, your email information remains strictly confidential with us. Let’s collaborate to enhance your operations today.

Ask For Quote Now!

Ask For A Quick Quote

*we respect your confidentiality and all information are protected.