Omron Analog Input Unit CJ1W-AD041-V1

Analog input unit, 4 x inputs 1 to 5 V, 0 to 5 V, 0 to 10 V, -10 to 10 V, 4 to 20 mA, resolution 1:4000 / 8000, screw terminal

BrandOmron
Model NumberCJ1W-AD041-V1
StateIn stock
ConditionNew Original
Warranty12 months

Categories

Global Assurance

100% new original
12 months warranty
wordwide shipping
ItemCJ1W-AD041-V1CJ1W-AD081-V1CJ1W-AD042
Unit typeCJ-series Special I/O Unit
Isolation *1Between I/O and Controller signals: Photocoupler (No isolation between I/O signals.)Between I/O and Controller signals: Digital isolator (No isolation between I/O signals.)
External terminals18-point detachable terminal block (M3 screws)
Power consumption420 mA max. at 5 VDC520 mA max. at 5 VDC
Dimensions (mm)31 × 90 × 65 mm (W × H × D)
Weight140 g max.150 g max.
General specificationsConforms to general specifications for CJ Series.
Input specifi- cationsNumber of analog inputs484
Input signal range *21 to 5 V 0 to 5 V 0 to 10 V – 10 to 10 V 4 to 20 mA *31 to 5 V 0 to 10 V – 5 to 5 V – 10 to 10 V 4 to 20 mA *4
Maximum rated input (for 1 point) *5Voltage Input: ± 15 V Current Input: ± 30 mA
Input impedanceVoltage Input: 1 MΩ min. Current Input: 250 Ω (rated value)
Resolution4,000/8,000 *61 to 5 V10,000
0 to 10 V20,000
– 5 to 5 V20,000
– 10 to 10 V40,000
4 to 20 mA10,000
Converted output data16-bit binary data
Accuracy *725 °C *8Voltage Input: ± 0.2% of F.S. Current Input: ± 0.4% of F.S.
0 °C to 55 °CVoltage Input: ± 0.4% of F.S. Current Input: ± 0.6% of F.S.
A/D conversion period *91 ms/250 μs per point *620 μs/1 point, 25 μs/2 points, 30 μs/3 points, 35 μs/4 points
Input functionsMean value processingStores tde last “n” data conversions in tde buffer, and stores tde mean value of tde conversion values. Buffer number: n = 2, 4, 8, 16, 32, 64Stores tde last “n” data conversions in tde buffer, and stores tde mean value of tde conversion values. Buffer number: n = 2, 4, 8, 16, 32, 64, 128, 256, 512
Peak value holdingStores tde maximum conversion value while tde Peak Value Hold Bit is ON.
ScalingSetting values in any specified unit witdin a range of ±32,000 as tde upper and lower limits allows A/D conversion to be executed and analog signals to be output witd tdese values as full scale.
Input disconnection detectionDetects tde disconnection and turns ON tde Disconnection Detection Flag. *10
Offset/gain adjustmentSupported
Direct conversionA/D conversion is performed and tde converted value is refreshed when tde ANALOG INPUT DIRECT CONVERSION instruction (AIDC) is executed. This instruction is supported by tde CJ2H-CPU[][](-EIP) CPU Units witd unit version 1.1 or later, and CJ2M-CPU[][]. CJ1, NJ501, and CP1H CPU Units and NSJ Controllers do not support direct conversion.

Get Started Today!

UNLOCK EFFICIENT SOLUTIONS – SUBMIT YOUR REQUEST FOR IMMEDIATE ASSISTANCE.

Embark on a journey of seamless procurement with us. If you’re seeking a product quote or require any additional support, our team is here to guide you every step of the way.

Fill out this form to start a conversation tailored to your specific needs. We understand the value of your project and time.

Rest assured, your email information remains strictly confidential with us. Let’s collaborate to enhance your operations today.

Ask For Quote Now!

Ask For A Quick Quote

*we respect your confidentiality and all information are protected.